Product Description
ETCR5000 3-Phase Energy Power Quality Analyzer Logger
Karya Mandiri Techindo has a wide range of ETCR products – search by type, or model, or filter by brand to find the one you are after. If you still can’t find it contact us..
ETCR5000 Power Quality Analyzer is a comprehensive test instrument carefully developed by our company and specially designed for field test of three phases, multi-functional and intelligent, concise man-machine operation. It is easy to use, large LCD screen display, high resolution, interface in both Chinese and English, shock-proof shell structure and so on.
Specifications ETCR5000 3-Phase Energy Power Quality Analyzer Logger
General Specification
Function | Description |
Power supply | Rechargeable lithium-ion battery packs 9.6V, backup charger |
Battery Level indicator | Battery symbol 5 grid Display power, when the battery level is low, automatically shut down after 1 minute indication |
Working Current | about 590mA, continuous working 8 hours |
Display mode | LCD color screen, 640dots × 480dots, 5.6 inches, display field 116mm × 88mm |
Instrument Size | 240mm×170mm×68 mm |
CT Size | 008B small sharpcurrent clamp: 7.5mm×13mm
040Bround jaw current clamp: 35mm×40mm 068Bround jaw current clamp: 68mm×68mm 300F Flexible Coil Current Sensor (with Integrator) : Ф300mm |
Number of channels | 4 voltages, 4 currents |
Line Voltage | 1.0V~2000V |
Phase Voltage | 1.0V~1000V |
Current | 008B current clamp: 10mA~10.0A
040B current clamp: 0.10A~100A 068B current clamp: 1.0A~1000A 300F Flexible Coil Current Sensor (with Integrator) : 10A ~ 6000A |
Frequency | 40Hz~70Hz |
Electricity Energy Parameter | W, VA, Var, PF, DPF, cosφ, tanφ |
Energy parameters | Wh, Varh, Vah |
Harmonic Wave | Yes, 0 – 50 times |
Total harmonic distortion | Yes, 0 – 50 times, each phase |
Expert Mode | Yes |
Transient Record Groups | 150 groups |
Voltage Flicker | Yes |
Start Current Mode | Yes, 100 seconds |
Three-phases Unbalance | Yes |
Record | 300 days (record 20 parameters simultaneously, every 5 seconds record 1 point) |
Min/Max Recorded Value | Yes, the max min value can be measured for a certain time |
Alarm | 40 different types of parameter selection, 12800 group alarm logs |
Peak | Yes |
Phasor Diagram Display | Automatic |
Screenshot Capacity | 60PCS |
Menu language | English/Chinese |
Communication Interface | USB |
Automatic Shut Down | In the alarm/trend graph recording/transient capture mode (waiting or in progress), the instrument does not automatically shut down |
In other test modes, there is no button operation within 15 minutes, prompting to automatically shut down after 1 minute | |
Backlight Function | Yes, suitable for dark places and nighttime use |
Instrument Weight | Host: 1.6kg (with battery) |
008B small sharpcurrent clamp: 170g×4 | |
040Bcircle current clamp: 190g×4 | |
068Bcircle current clamp: 510g×4 | |
300F Flexible Coil Current Sensor (with Integrator) : 330g×4 | |
Test wires and power adapter: 900g | |
Total weight: about 9.2kg (with package) | |
Voltage Test Wire Length | 3M |
Current Clamp Wire Length | 2M |
Working Temperature | -10°C~40°C; below 80%Rh |
Storage Temperature | -10°C~60°C; below 70%Rh |
Input Impedance | Test voltage input impedance: 1MΩ |
Withstand voltage | Withstand the sine wave AC voltage of 3700V/50Hz one minute between the instrument line and out shell |
Insulation | Between instrument line and shell ≥10MΩ |
Structure | Double insulation, with insulation shock-proof sheath |
SuitableSafely Standard | IEC 61010 1000V Cat III / 600V CAT IV, IEC61010-031, IEC61326, Pollution degree: 2. |
Accessories | Host: 1PCS; Instrument Bag: 1pcs; Test Cable: 5PCS (yellow, green, red, blue, black); Alligator Clip: 5PCS; Probe: 5PCS; Charger 1PCS; Software CD: 1COPY; 2G Memory Card: 1PCS. Current Clamp: (optional) |
KARYA MANDIRI TECHINDO adalah Supplier ETCR5000 3-Phase Energy Power Quality Analyzer Logger dan juga menjual Brand ETCR. Lihat produk kami lainnya di sini JSI, SGI, SMG atau hubungi kami lewat Whatsapp 0821-3010-0456 atau via email [email protected].